SR-2303FA-OLED
Product Data
- In compliance with IEC 62386-101:2014, IEC 62386-102:2014, IEC 62386-207 Ed2.
- Built-in DALI-2 interface, DALI DT6 device
- Match all DALI systems in the market
- DALI DT6 dimmer, 4 channels PWM output, built-in DALI master function
- OLED display interface , easy & fast installation
- No DALI master required for configuration
- Cost & time saving than DALI USB configuration
- DALI address quantity 1-4 settable for 4 PWM outputs
- Enables to address & group 4 PWM outputs individually
- Enables to predefine & recall 16 DALI scenes to 4 PWM outputs individually
- Logarithmic/Linear dimming curve settable, match sensitivity of human eyes
- 250Hz-30KHz PWM frequency settable, flicker free, no noise
- Enables to set a min. level for dimming between this level to max. level
- Enables to manually set output level for 4 PWM outputs individually
- Enables to set fade Time, fade rate, power on level, system failure level
Send Enquiry Now
Input Voltage | 12-36VDC |
Output Current | 4 x 5A |
Output Power | 4x(60-180)W |
DALI Consumption | 2mA |
Remarks | Constant voltage |
Connector Current Rating | Max. 20A |
Size(LxWxH) | 170x53.4x28mm |
Ambient Temperature | -20℃ ~ +50℃ |
After wiring the dimmer correctly, power on it, the OLED will show means 4 PWM channels with 4 DALI addresses (00, 01, 02, 03) by factory default. Then click “Menu” button to
enter Menu Select interface, keep clicking “Up” and “Down” buttons, you will get commissioning and configuration options one by one on the OLED display as follows:
1.Set Addr: assign DALI addresses to 4 PWM outputs
2.Set Group: assign 4 PWM outputs to one or more DALI groups
3.Save Scene: configure up to 16 scenes (0–15) to 4 PWM outputs
4.go to Scene: recall the configured 16 scenes to 4 PWM outputs
5.Set Dir Power: set out level of 4 PWM outputs manually
6.Set curve: set the dimming curve
7.Set Time Rate: set fade time and fade rate
8.Set Power Min: set a minimum level, the dimmer can not be dimmed below this value
9.Set Power on: set a level as the value after power is restored
10.Set Sys fail: set a level as the value in the event of failure of the DALI power supply
11.Set Channel: set DALI address quantity for 4 PWM outputs
12.Set Zero Addr: set the starting DALI address as 0/1
13.Set PWM freq: set the output PWM frequency
14.Reset: factory reset the dimmer